Backflow Test Report Template

Fill in the assembly, the readings and your certificate number, sign it, and download a PDF for the customer. Works for RP, DC, PVB and SVB assemblies.

Backflow test report

Saved in this browser only. Nothing is sent to us.

Property and water supplier

Assembly

Initial test

Repairs and retest

Result and tester

Readings say-
Tester signature

Pass values follow the common minimums in the USC Manual of Cross-Connection Control, 10th edition. Your water supplier's form and rules come first.

Doing this every week?

Book, test, report and bill in one place

Clevra runs the business side of a backflow testing company. It doesn't file with water suppliers, so you still file the way your supplier asks.

Recurring visits don't repeat yearly yet, so book next year's test on its due date. See Clevra for backflow testing.

How to fill in the report

  1. 1

    Assembly details

    Type, make, model, serial and size, plus where it sits and what it protects.

  2. 2

    Readings

    Enter each reading in psid. The form flags anything below the common minimum and works out pass or fail.

  3. 3

    Sign and download

    Add your certificate number and test kit, sign on the screen and download the PDF.

Reference

Common passing values

These are the field test minimums in the USC Foundation's Manual of Cross-Connection Control, 10th edition. Your water supplier's form and rules come first.

AssemblyTestMinimum
RPRelief valve opening point2.0 psid
RPCheck valve 15.0 psid, and above the relief valve reading
RPCheck valve 2Closes tight against backpressure
DCCheck valve 11.0 psid
DCCheck valve 21.0 psid
PVB and SVBAir inletOpens at 1.0 psid and opens fully
PVB and SVBCheck valve1.0 psid

What a complete report has

  • The property, the assembly location and what it serves.
  • Type, make, model, serial number and size.
  • Initial readings, then repairs and retest readings if it failed.
  • Your certificate number, the test kit and its calibration date.
  • Pass or fail, the date and your signature.

Backflow test report FAQ

Will my water supplier accept this report?

Some will and some won't. Many suppliers want reports on their own form or filed in their own online system. Use this as the customer copy and your own record, and file with the supplier the way they ask.

What readings pass a backflow test?

Under the USC Manual of Cross-Connection Control, 10th edition: an RP relief valve opens at 2.0 psid or more, check valve 1 holds 5.0 psid or more and above the relief valve reading, and check valve 2 closes tight. Each check on a double check holds 1.0 psid or more. A PVB or SVB air inlet opens at 1.0 psid or more and opens fully, and the check holds 1.0 psid or more.

My supplier's form asks for a 3.0 psid buffer. Which is right?

Follow your supplier. Older criteria and some local forms still want check valve 1 to read at least 3.0 psid above the relief valve opening point. The 10th edition dropped that buffer, but the supplier sets the rules for its system.

Does it work for RPDA and DCDA assemblies?

Yes. Pick the detector type, record the main assembly readings, and put the bypass meter details in the comments.

Do you keep my reports or tester details?

No. Everything stays in your own browser, so your name and certificate number are filled in next time. Nothing is sent to Clevra.

Cta Dot Bg

All-in-one operations platform for trades.

You run a crew, not a tech company. Clevra handles the office stuff so you can stay on the tools.