
A generator maintenance checklist lists the inspections, tests and service a standby generator needs, by interval, so it starts and carries the load when the power fails. For emergency and legally required systems, NFPA 110 sets the minimum. For home standby units, the manufacturer's schedule does.
The checklist below works for both, with the NFPA 110 items called out. Hospitals and other healthcare sites may also answer to NFPA 99 and their accreditor, and the edition your authority having jurisdiction (AHJ) has adopted is the one that counts.
Reviewed November 6, 2026.
NFPA 110 asks for diesel units to run at least 30 minutes a month under a load that either reaches the manufacturer's recommended exhaust temperature or is at least 30 percent of the nameplate kW rating. Record on every run:
Operate the automatic transfer switch on the monthly test, so the switch is proved as well as the engine.
A load bank test runs the generator against an artificial load to prove it can carry its rating and to burn off deposits from running light. NFPA 110 calls for one each year on diesel units whose monthly runs can't meet the 30 percent load or exhaust temperature requirement. Running too lightly for too long causes wet stacking, where unburned fuel builds up in the exhaust.
The steps depend on the edition your AHJ uses. An older edition still followed at many healthcare sites runs 25 percent for 30 minutes, 50 percent for 30 minutes and 75 percent for 60 minutes, two hours in all. Newer editions run 50 percent for 30 minutes and then 75 percent for 60 minutes. Record readings at regular intervals through the test and attach them to the report.
Most home standby generators run a short self-test on a timer, often every week, and need a yearly service: oil and filter, air filter, spark plugs, a battery check and a test under load through the transfer switch. Follow the maker's schedule, which often sets oil changes by run hours too, and service the unit after any long outage.
Set each contract up as a recurring job in Clevra, quarterly or semiannual, so every visit lands on the schedule without anyone rebooking it. Build a checklist with number fields for hours, voltage, frequency and load, photo questions and a signature, and attach it to the service so it comes with every visit.
Checklists and reports come with Pro and Business. See generator maintenance software, electrical contractor software and our guide to maintenance agreements for recurring revenue.
NFPA 110 calls for emergency generators to run under load at least monthly for 30 minutes. Home standby units usually run a short automatic self-test on a timer set by the manufacturer, often weekly.
A weekly inspection, a monthly test run and a full service at least once a year, with oil changes by run hours on units that run often.
A test that runs the generator against an artificial load to prove it carries its rating. NFPA 110 calls for one each year on diesel units whose monthly runs don't reach 30 percent of nameplate or the right exhaust temperature.
A buildup of unburned fuel and soot in a diesel generator's exhaust, caused by running at light load for long periods. Running under proper load, or a load bank test, burns it off.
Fluid levels, batteries, leaks, exhaust, the control panel and transfer switch, test run readings, parts replaced and the next due date, organized by weekly, monthly and annual tasks.
Build the checklist once, set up one contract as a recurring job, and send the service report before you leave the site. The Free plan has no end date, and Pro or Business are free for 14 days, no card needed.
Get Started for Free or Book a Demo.
Sources: Kansas State Fire Marshal, Generator Testing (Fire Fact 082); NFPA 110, Standard for Emergency and Standby Power Systems.

You run a crew, not a tech company. Clevra handles the office stuff so you can stay on the tools.